UNDERWRITERS
LABORATORIES INC. APPLIANCE WIRING MATERIAL
Subj. 758 Section 1 Page 1015 Issued:
1959-05-01
Revised:
2003-02-17
Style
1015 PVC Insulated Wire.
_________________________________________________________________
Rating 80°C, 90°C or 105°C;
600 V ac, 750 V dc.
_________________________________________________________________
Conductor 30 AWG - 2000 kcmil.
_________________________________________________________________
Insulation PVC
Min. Avg. Min at Any Point
Size Mils Mils
30-9 30
27
8,7 45
40
6-2 60
54
1-4/0 80
72
250-500 kcmil 95 86
550-1000 kcmil 110
99
1100-2000 kcmil 125 112
_________________________________________________________________
Standard Appliance Wiring Material UL 758.
Standard Appliance Wiring Material UL 758.
_________________________________________________________________
Instructions Detailed Examination.
to UL Physical Properties, unaged, Class
43.
Representative Spark Test.
_________________________________________________________________
UL (4) Detailed Examination.
Counter-Check (4)
Physical Properties, Class 43.
Program (4)
Heat Shock.
(4) Cold Bend.
(4)
Deformation.
* (12) Horizontal Flame Test.
_________________________________________________________________
Marking General.
_________________________________________________________________
Use Internal Wiring of Appliances; or
Internal Wiring of
Appliances where exposed to oil at a temperature not exceeding
60 deg. C or 80 deg. C (whichever is applicable). Tags may also indicate the following: 2,500 V
peak - for electronic use only.
No comments: