APPLIANCE
WIRING MATERIAL
Subj.758 Section 2 Page 2517 Issued:1970-10-21
Revised:2013-03-04
Revised:2013-03-04
Style 2517 Multiple-conductor
cable using non-integral jacket
Rating
|
105
deg C, 300 Vac, Cable Flame.
|
Insulated
Conductor
|
Labeled
or complying with Manufacturer's AWM Procedure. 40 AWG minimum.
|
Assembly
|
Consists
of two or more singles, twisted pairs or groups of twisted singles twisted
together. The singles or groups of singles may be laid parallel forming a
flat, oval or round cable. The lay of the conductors are not specified. A
barrier layer and/or fillers are optional. Manufacturer shall maintain a
complete description of each assembly. May use same or mixed AWG size.
|
Covering
|
Optional.
|
Shield
|
Optional.
|
Jacket
|
Extruded
PVC.
|
|
Diameter of Core Assembly
under Jacket@
|
Minimum Average Thickness
|
Minimum Thickness at any
point
|
0.700 inch or less
|
30 mils
|
24 mils
|
0.701 - 1.000 inch
|
45 mils
|
36 mils
|
1.001 - 1.500 inch
|
60 mils
|
48 mils
|
1.501 - 2.500 inch
|
80 mils
|
64 mils
|
Covering
|
Optional,
braid.
|
Standard
|
Appliance
Wiring Material UL 758.
|
Marking
|
General.
|
Use
|
External
interconnection of electronic equipment or internal wiring of electronic
equipment or appliances. Tags may also indicate the following: "600
Volts peak for Electronic Use Only".
|